Check manual page of cmciii_lcp_waterflow


Rittal CMC-III LCP: Water Flow

Distribution: official part of Check_MK
License: GPL
Supported Agents: SNMP

This check monitors the water flow of Rittal CMC-III LCP devices. No limits are set in the check, since limits are configured in the Rittal device itself. The state given by the Rittal device is taken as the state of the check as follows: If the Rittal device returns OK, the check is OK. Otherwise the check is CRIT. Furthermore, the minimum and maximum flow limits of the device are extracted and a state of WARN is assumed if the actual flow is outside these limits.

Item

None

Discovery

None