Check manual page of ups_test


Generic UPS Device: Self Test

Distribution: official part of Check_MK
License: GPL
Supported Agents: SNMP


This check monitors parameters related to the self test of UPS devices: the result of the last self test and the last date of the self test run. The check becomes CRIT if the test result is "doneError" or "aborted", and WARN if the result is "doneWarning" or "noTestsInitiated". It also has a WARN or CRIT state if the date of the last self test is more than the warning or critical level ago.

Discovery

The inventory process checks if the device has a system description OIDs (.1.3.6.1.2.1.1.2.0) and if the name of this OID is known to the test. If this is true the system is inventorized.